Descripción del producto
The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Datos técnicos
Conexión
- Caja
- Polyesterdose (PO)
Propiedades
- Clase de protección
- IP 65
- Entrada de cable
- PVDF-Verschraubung , PVC-Dichtung
- Material del flotador
- PE
- Material de la base de la sonda de fugas
- PE
- Cable
- TPK (PVC Basis)
- Temperatura de funcionamiento
- max. 60 °C
- Presión de funcionamiento
- atmosphärisch
- Densidad del medio
- ρ ≥ 0,6 g/cm³
- Histéresis de conmutación
- typ. 2 mm
- Tolerancia del punto de conmutación
- max. 2 mm
Fuente de alimentación
- Voltaje nominal
- 24…230 V AC/DC
- Consumo eléctrico
- ≤ 2 W
Salidas
- Contacto de salida
- 2 potentialfreie Wechselkontakte
- Voltaje de conmutación
- max. 250 V AC / 30 V DC
- Corriente de conmutación
- max. 5 A AC / 5 A DC
- Capacidad de conmutación
- max. 750 VA / 90 W
- pantallas
- Betriebs-LED grün, Funktions-LED rot
- Retardo de conmutación
- ca. 0,5 s Anzug/Abfall
- Marcado CE
- siehe Konformitätserklärung
T-200.L 230V Configurar
Su configuración
- Designación básica
- T200L
- Länge
- Auswerteelektronik
- Anschlussgewinde
- Befestigungswinkel
- Schwimmertyp
Más información del producto
The T-200.L (24...230 V AC/DC) may be used, among other things, as leakage probes in the space between a tank and its associated catch basin. The float switches the reed contacts mounted in the guide tube via a magnet system when the liquid level rises. The resistance change in the sensor circuit of the electronic part triggered by the switching operation is evaluated and the output relay is activated. The electronic part ET-580a is mounted in the junction box.
The output relay operates in closed-circuit mode, i.e. in the event of an alarm, the output relay drops to the alarm position.
System structure
The leakage probe T-200.L (24...230 V AC/DC) can be connected to our "Optical Acoustic Alarm Devices" of the type series OAA-300.. (see section 01).
- Simple structure
- Rugged design
- Small dimensions
- Low system costs
- Interference free measurement
- High chemical resistance
- Functionally identical to the overfill protection of the "T-200.F..." series
- Evaluation in the connection head
- Problem-free, variable installation (rope design)
- Unproblematic setting and checking
- Supply voltage 24...230 V AC/DC
Documentos y descargas
Hoja de datos
Instrucciones de ajuste
Instrucciones de seguridad
Descripción técnica
Certificado de prueba
Declaración de conformidad
Accesorios
OAA-300
Ir al producto