T-200.L 230V

Leakage probes with general building authority approval

Features

WHG Leckagesonde

product family

level measurement

product class

overfill protection and leackage detector

suitable for

fluids

measurement principle

Schwimmer


Special characteristics

  • Approved for liquids hazardous to water

  • High chemical resistance

  • Interference-free measurement

Description

The leakage probes T-200.L are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.

Technical Data

Connection
Box
Polyesterdose (PO)
Properties
Protection class
IP 65
Cable entry
PVDF-Verschraubung , PVC-Dichtung
Material Float
PE
Material leakage probe base
PE
Cable
TPK (PVC Basis)
Operating temperature
max. 60 °C
Operating pressure
atmosphärisch
media density
ρ ≥ 0,6 g/cm³
Switching hysteresis
typ. 2 mm
Switching point tolerance
max. 2 mm
Power supply
nominal voltage
24…230 V AC/DC
Power consumption
≤ 2 W
Output
Output contact
2 potentialfreie Wechselkontakte
Switching voltage
max. 250 V AC / 30 V DC
Switching current
max. 5 A AC / 5 A DC
Switching capacity
max. 750 VA / 90 W
displays
Betriebs-LED grün, Funktions-LED rot
Switching delay
ca. 0,5 s Anzug/Abfall
CE marking
siehe Konformitätserklärung

T-200.L 230V configuration

T200L 1 - 2 - 3 - 4 - 5

1 Länge

  • 01 : 1 Meter
  • 02 : 2 Meter
  • XX : Wunschlänge, bitte angeben

2 Auswerteelektronik

  • 230 : mit Elektronikteil ET-580a

3 Anschlussgewinde

  • G2 : G2"
  • 1 : G1"
  • 125 : G1¼"
  • 15 : G1½"
  • GF : G2¾" Überwurfmutter
  • 0 : ohne Verschraubung

4 Befestigungswinkel

  • 0 : keiner
  • B : Befestigungswinkel bitte angeben

5 Schwimmertyp

  • PE : PE 52

Further product information

The T-200.L (24...230 V AC/DC) may be used, among other things, as leakage probes in the space between a tank and its associated catch basin. The float switches the reed contacts mounted in the guide tube via a magnet system when the liquid level rises. The resistance change in the sensor circuit of the electronic part triggered by the switching operation is evaluated and the output relay is activated. The electronic part ET-580a is mounted in the junction box.

The output relay operates in closed-circuit mode, i.e. in the event of an alarm, the output relay drops to the alarm position.

System structure

The leakage probe T-200.L (24...230 V AC/DC) can be connected to our "Optical Acoustic Alarm Devices" of the type series OAA-300.. (see section 01).

  • Simple structure
  • Rugged design
  • Small dimensions
  • Low system costs
  • Interference free measurement
  • High chemical resistance
  • Functionally identical to the overfill protection of the "T-200.F..." series
  • Evaluation in the connection head
  • Problem-free, variable installation (rope design)
  • Unproblematic setting and checking
  • Supply voltage 24...230 V AC/DC

 

Documents and Downloads

Accessoires

Our application engineers advise you personally, comprehensively and professionally!

Simply contact us by phone or e-mail!

Call us right away!

+49-6251-8462-0

contact form

Logo of Fluid.iO Sensor + Control

Fluid.iO
Sensor + Control
GmbH & Co. KG

An der Hartbrücke 6
64625 Bensheim
Tel.: +49-6251-8462-0
E-Mail: info@fluidio.de