Description
The programmable digital display AD-31… can be used in all applications through the parameterization capability of the input values and the display area.
Technical Data
Properties
- Protection class EN60529 clamp
- IP 20
- Protection class EN60529 front panel
- IP 65
- Operating temperature
- – 20...+ 60 °C
- nominal voltage
- Weitbereichsnetzteil; 20 V DC ... 230 V AC
- Power consumption
- max. ca. 3 VA
- Output contact
- 2 Schließer / NO
- Switching voltage
- max. 250 V AC, 300 V DC
- Switching current
- max. 3 A , DC min. 30 mA
- Switching capacity
- max. 50W, 100 VA
- Unregulated auxiliary voltage source
- 15...20 V DC / 20 mA
- Display
- LED 14 mm, 5-stellig
- Dimensions
- 96x48x100 mm
- Weight
- ca. 200 g
- Panel cut-out
- H:45+0,6mm, B:92+0,8 mm
Equipment
- Measuring input current
- 0(4)...20 mA DC
- Measuring input voltage
- 0(2)...10 V DC
- Measuring input Potentiometric voltage divider
- 1...100 kΩ
- Display
- LED 14 mm, 5-stellig
- operation
- Folientasten
- Display range
- -19999...32000
- data backup
- EEPROM
- measurement uncertainty
- ±1 % oder ±1 Digit
- analogue output
- 0 (4)...20 mA
AD-310 configuration
Your Configuration
- Basename
- AD-31
- Grenzkontakte
- Versorgungsspannung
- Schnittstelle
Further product information
The input circuit allows for direct connection of transmitters with voltage output (0(2)…+ 10 V, with current output 0(4)…20 mA or resistance remote transmitters, such as level measuring transmitters with resistance chains. Device-internal auxiliary voltage sources are available to supply electrodes, sensors in two or three wire technology and resistance remote transducers.