Description
The leakage probes T-200.L (24 V) are approved by the "DIBt" on the basis of the "WasBauPVO" for the detection of leaked liquids hazardous to water.
Technical Data
Connection
- Box
- Polyesterdose (PO)
- Head
- Polyethylenanschlusskopf (PE)
Properties
- Protection class
- IP 65
- Cable entry
- PVDF-Verschraubung , PVC-Dichtung
- Material Float
- PE
- Material leakage probe base
- PE
- Cable
- TPK (PVC Basis)
- Operating temperature
- max. 60 °C
- Operating pressure
- atmosphärisch
- media density
- mit Schwimmer PE 52 ρ ≥ 1,05 g/cm³
- Switching hysteresis
- typ. 2 mm
- Switching point tolerance
- max. 2 mm
Power supply
- nominal voltage
- 24 V DC (24...30 V DC)
- Power consumption
- ≤ 1 W
Output
- Output contact
- 1 potentialfreier Wechselkontakt
- Switching voltage
- max. 250 V AC / 30 V DC
- Switching current
- max. 3 A AC / 3 A DC
- Switching capacity
- max. 750 VA / 90 W
Optocoupler
- Switching voltage
- max. 30 V
- Switching current
- max. 100 mA
- displays
- Betriebs-LED grün, Funktions-LED rot
- Switching delay
- ca. 0,5 s Anzug/Abfall
T-200.L 24V configuration
Your Configuration
- Basename
- T200L
- Länge
- Anschluss
- Anschlussgewinde
- Befestigungswinkel
- Schwimmertyp
Further product information
The T-200.L (24 V) may be used, among other things, as leakage probes in the space between a tank and its associated sump.
The float switches the reed contacts mounted in the guide tube via a magnetic system when the liquid level rises. The change in resistance in the sensor circuit of the contact protection relay triggered by the switching operation is evaluated and the output relay is triggered. As "evaluation unit" the electronic part ET-52xx is mounted directly in the connection head/socket.
The output relay operates in closed-circuit mode, i.e. in the event of an alarm the output relay drops to the alarm position. The evaluation circuit is additionally equipped with a semiconductor switch (opto-coupler) (low switching currents (20 mA), e.g. PLC systems).
- Simple structure
- Rugged design
- Small dimensions
- Low system costs
- Interference free measurement
- High chemical resistance
- Functionally identical to the "T-200.F ..." series overfill prevention device.
- Evaluation in the connection head
- Problem-free, variable installation (rope version)
- Unproblematic setting and checking
Reed sensor | LED Green | Light emitting diode red | Switching function |
≈ 1 kΩ | A | From | Ready for operation |
≈ 12 kΩ | A | A | Leak alarm |
<1 kΩ | From | A | Short circuit alarm |
>12 kΩ | From | A | Leakage interruption alarm |
- / - | From | From | Voltage alarm |
Documents and Downloads
Data sheet
Settings instructions
Safety instructions
technical description
declaration of conformity
Accessoires