Description
Level sensors type T-20_.F... are approved by the DIBt (German Institute for Structural Engineering) as liquid level limit switches for the overcharge protection of containers for storing water-dangerous liquids.
Données techniques
Raccordement
- Boîte
- Polyester
Propriétés
- Classe de protection EN60529
- IP 65
- filetage de raccordement
- G 1", G 1¼", G 1½", G2", G3”
- Écrou-raccord
- G 2¾", S 100x8
- Longueur du tube de guidage
- max. 6 m
- Température de fonctionnement
- max. 80°C
- Pression de fonctionnement
- atmosphärisch
- Densité du fluide
- ρ ≥ 0,6 g/cm³ (je nach Schwimmertyp)
- Hystérésis de commutation
- typ. 2 mm
- Tolérance du point de commutation
- max. 2 mm
Alimentation électrique
- tension nominale
- 24…230 V AC/DC
- Consommation électrique
- ≤ 2 W
Sorties
- Contact de sortie
- 2 potentialfreie Wechselkontakte
- Tension de commutation
- max. 250 V AC / 30 V DC
- Courant de commutation
- max. 5 A AC / 5 A DC
- Capacité de commutation
- max. 750 VA / 90 W
- affichages
- Betriebs-LED grün, Funktions-LED rot
- Retard de commutation
- ca. 0,5 s Anzug/Abfall
- Marquage CE
- siehe Konformitätserklärung
T-20x.F 230V configuration
Votre configuration
- Nom de la base
- T20
- Führungsrohr
- Sicherheitsfunktion
- Rohrmaterial
- Anschlussgewinde
- Ausführung
- Schwimmermaterial
- Anschluss-Elektronikteil
- Länge
Autres informations sur les produits
The floater switches the reed contact mounted in the guide tube when the liquid level rises. The change in resistance in the sensor circuit resulting from the switching operation is evaluated and the output relay triggered.
Parts of the level sensor which get into contact with the media are completely made of PE, PP, PVC, PVDF. So the level sensors T-20_.F... are perfectly suited for being used with tanks for storing highly aggressive media.
The overfill cut-out device consists of the level sensor and the measuring transducer. Our “contact protective relays” type KR-163... and KR-268..., which are also approved by the DIBt, can be used as corresponding measuring transducers (see section 10). The level sensors T-20_.F... can be connected to our “alarm indicators” type OAA-100 and OAA-300.
- Easy to install
- Sturdy design
- Small dimensions
- Interference-proof measurement
- Switching point adjustable
- Various options for connection (connector box / plug / cable)
- For usage in category 2 (Ex zone 1) (in combination with [Ex]i contact protective relay KR-163/A/Ex)
- Short-line fault / open circuit monitoring (in combination with contact protective relay KR-163... and KR-268... / alarm indicator OAA-100...)
- Under the F-contact further optional switching points can be realized
- Under the F-contact its also possible to integrate a continuous measurement
Documents et téléchargements
Instructions de configuration
Consignes de sécurité
Certificat de contrôle
Vidéo sur le produit
Accessoires
OAA-300
Voir le produit